Multiquip Portable Generator DCA45SSI User Manual

ꢀ DCA45SSI  
MQ POWER Series Generator  
WhisperWatt™  
Prime Rating — 36 kW (45 kVA)  
standby Rating — 40 kW (50 kVA)  
Three-Phase, 60 Hertz, 0.8 PF  
45  
standaRd FEatuREs  
„ Heavy duty, 4-cycle, direct injection, diesel engine provides  
maximum reliability.  
„ Automatic start/stop control — automatically starts the  
generator set during a commercial power failure when used  
in conjunction with a transfer switch.  
„ Brushless alternator reduces service and maintenance  
requirements and meets temperature rise standards for Class  
H insulation systems.  
„ Complete generator analog instrumentation includes voltage  
regulator control, ammeter phase selector switch, voltmeter  
phase selector switch, AC voltmeter, AC ammeter, frequency  
meter, panel light, and circuit breaker.  
„ Open delta excitation design provides virtually unlimited  
excitation for maximum motor starting capability.  
„ Automatic voltage regulator (AVR) provides precise regulation.  
„ Automatic safety shutdown system monitors the water  
temperature, engine oil pressure, overspeed and overcrank.  
Warning lights indicate abnormal conditions.  
„ Electronic Governor Control — maintains frequency to within  
0.25% from no load to full load.  
„ Complete power panel. Fully covered;three-phase terminals  
and single phase receptacles allow fast and convenient  
hookup for most applications including temporary power  
boxes, tools and lighting equipment. The GFCI receptacles  
are NEMA 5-20, and the auxilillary outputs use CS6369 twist-  
lock receptacles.  
„ Full load acceptance of standby nameplate rating in one step  
(NFPA 110, para 5-13.2.6).  
„ Sound attenuated, weather resistant, steel housing provides  
operation at 65 dB(A) at 23 feet. Fully lockable enclosure  
allows safe unattended operation.  
„ Internal fuel tank with direct reading of fuel gauge.  
„ Simultaneous single and three phase power.  
„ Seven stage powder coat paint system provides durability  
and weather protection.  
„ Voltage selector switch offers the operator a wide range of  
voltages that are manually selectable. Fine tuning of the  
output voltage can be accomplished by adjusting the voltage  
regulator control knob to obtain the desired voltage.  
„ Fuel/water separator removes condensation from fuel for  
extended engine life. Panel mounted alarm light included.  
„ Complete engine analog instrumentation includes DC  
ammeter, oil pressure gauge, water temp. gauge, fuel level  
gauge, tachometer/hour meter, preheat indicator, emergency  
shutdown monitors.  
„ EPA emissions certified - Interim Tier 4 emissions compliant.  
dca45ssi — MQ POWER sERiEs gEnERatOR — REv. #12 (08/23/11)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ꢀ DCA45SSI  
MQ POWER Series Generator  
sPEciFicatiOns  
Cooling System  
Fan Load  
0.94 hp (0.7 kW)  
2.96 gallons (11.2 liters)  
15.4 gallons (58.5 liters)  
1640 Btu (1.73 MJ)  
379 Btu (0.40 MJ)  
6.1 psi (42 kPa)  
Generator Specifications  
Coolant Capacity (with radiator)  
Coolant Flow Rate (per minute)  
Heat Rejection to Coolant (per minute)  
Heat Rejection to Room (per minute)  
Maximum Coolant Friction Head  
Maximum Coolant Static Head  
Ambient Temperature Rating  
Revolving field, self-ventilated  
Drip-proof, single bearing  
Design  
Armature Connection  
Phase  
Star with Neutral  
3
Zig Zag  
Single  
Standby Output  
Prime Output  
40 KW (50 KVA)  
36 KW (45 KVA)  
27.6 KW  
26 KW  
21 feet (6.4 meters)  
104°F (40°C)  
3Ø Voltage (L-L/L-N)  
Voltage Selector Switch at 3Ø 240/139  
208Y/120, 220Y/127,  
240Y/139  
N/A  
N/A  
3Ø Voltage (L-L/L-N)  
Voltage Selector Switch at 3Ø 480/277  
416Y/240, 440Y/254,  
480Y/277  
Air  
1Ø Voltage (L-L/L-N)  
(Voltage Selector Switch at 1Ø 240/120)  
N/A  
0.8  
240/120  
1.0  
Combustion Air  
Maximum Air Cleaner Restriction  
Alternator Cooling Air  
99 cfm (2.8 m3/min)  
25 in. H2O (6.25 kPa)  
526 cfm (14.9 m3/min)  
2330 cfm (66 m3/min)  
Power Factor  
Voltage Regulation (No load to full load)  
Generator RPM  
0.5%  
1800  
60 Hz  
4
Radiator Cooling Air  
Frequency  
Exhaust System  
No. of Poles  
Gas Flow (full load)  
233 cfm (6.6 m3/min)  
896°F (480°C)  
Excitation  
Brushless with AVR  
60 Hz  
Frequency  
Gas Temperature  
Frequency Regulation:  
No Load to Full Load  
Isochronous under varying loads from  
no load to 100% rated load  
Maximum Back Pressure  
53.2 in. H2O (13.3 kPa)  
0.25% of mean value for constant loads  
from no load to full load.  
Amperage  
Frequency Regulation: Steady State  
Rated voltage  
Maximum amps  
Insulation  
Class H  
65  
100 Amps (4 wire)  
108A x 2 (Zigzag)  
Sound Level dB(A) Full load at 23 feet  
1Ø 120 Volt  
50 Amps (4 wire)  
108A (Zigzag  
1Ø 240 Volt  
Engine Specifications  
Make / Model  
Emissions  
Isuzu / BU-4JJ1T  
EPA Interim Tier 4 Certified  
Electric  
3Ø 240 Volt  
3Ø 480 Volt  
108 Amps  
54 Amps  
110 Amps  
Starting System  
Main Line Circuit Breaker Rating  
4-cycle, water cooled,  
direct injection, turbocharged  
Design  
Over Current Relay Trip Set Point  
480V Mode Only  
54 Amps  
Displacement  
No. cylinders  
183.0 in3 (2999 cc)  
4
WaRRanty*  
isuzu Engine  
Bore x Stroke (mm)  
Gross Engine Power Output  
BMEP  
95.4 x 104.9  
67.1 bhp (50 kW)  
136 psi (940 kPa)  
1237 ft./min. (6.29 m/s)  
17.5:1  
12 months from date of purchase with unlimited hours or 24 months  
from date of purchase with 2000 hours (whichever comes first).  
Piston Speed  
Compression Ratio  
Engine Speed  
Overspeed Limit  
Oil Capacity  
1800 rpm  
generator  
24 months from date of purchase or 2000 hours (whichever occurs first).  
2100 rpm  
2.25 gallons (8.5 liters)  
12V 72Ah x 1  
trailer  
12 months excluding normal wear items.  
Battery  
*Refer to the express written, one-year limited warranty sheet for additional information.  
Fuel System  
Recommended Fuel  
Maximum Fuel Flow (per hour)  
Maximum Inlet Restriction (Hg)  
Fuel Tank Capacity  
Fuel consumption  
At full load  
ASTM-D975-No.1 & No.2-D  
16 gallons (61 liters)  
5.9 in. (150 mm)  
NOTICE  
Generator is not intended for use in enclosed areas or where free  
flow of air is restricted.  
26.5 gallons (100 liters)  
gph  
2.8  
2.1  
1.5  
0.9  
lph  
10.6  
8.0  
Backfeed to a utility system can cause electrocution, shock and/  
or property damage. dO nOt connect to any building’s electrical  
system except through an approved device.  
At 3/4 load  
At 1/2 load  
5.6  
Specifications are subject to change without notice.  
At 1/4 load  
3.4  
dca45ssi — MQ POWER sERiEs gEnERatOR — REv. #12 (08/23/11)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ꢀ DCA45SSI  
MQ POWER Series Generator  
OPtiOnal gEnERatOR FEatuREs  
„ Battery charger — provides fully automatic and self-  
adjusting charging to the generator's battery system.  
„ Jacket Water Heater — for easy starting in cold weather  
climates.  
„ special Batteries — long life batteries provide extra engine  
cranking power.  
„ low coolant level shutdown provides protection  
from critically low coolant levels. Includes control panel  
warning light.  
„ spring isolaters — provides extra vibration protection for  
standby applications.  
gEnERatOR OutPut PanEl  
„ trailer Mounted Package — meets National Highway  
Traffic Safety Administration (NHTSA) regulations. Trailer is  
equipped with electronic or surge brakes with double or triple  
axle configuration.  
OPtiOnal cOntROl FEatuREs  
„ Emergency stop switch — when manually activated shuts  
down generator in the event of an emergency.  
„ audible alarm alerts operator of abnormal conditions  
OPtiOnal OutPut cOnnEctiOns  
„ cam-lok connectors — provides quick disconnect  
alternative to bolt-on connectors.  
„ Pin and sleeve connectors — provides industry standard  
connectors for all voltage requirements.  
„ Output cable — available in any custom length and size  
configuration.  
OPtiOnal FuEl cEll FEatuREs  
„ trailer Fuel tank — a second fuel cell located in the  
trailer allows for extended run time.  
„ sub-base Fuel cells (double Wall) — Additional fuel  
cell for extended runtime operation. Contains a leak sensor,  
low fuel level switch, and a secondary containment tank.  
UL142 listed.  
„ 12 hours of minimum run time.  
„ 24 hours of minimum run time.  
dca45ssi — MQ POWER sERiEs gEnERatOR — REv. #12 (08/23/11)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ꢀ DCA45SSI  
MQ POWER Series Generator  
diMEnsiOns  
Weight  
Dry Weight  
Wet Weight  
2,227 lbs. (1,010 kg)  
2,464 lbs. (1,117 kg)  
Max. Lifting  
Point Capacity  
5,150 lbs. (2,335 kg)  
Generator can be placed on  
MQ Power Models TRLR70,  
TRLR70XF, TRLR75XF, and  
TRLR85XFTrailers.  
Manufactured by Denyo Co.  
Your Multiquip dealer is:  
MultiQuiP  
POST OFFICE BOx 6254  
CARSON, CA 90749  
310-537-3700 • 800-883-2551  
FAx: 310-604-3831  
© COPYRIGHT 2011 MULTIQUIP INC.  
DCA45SSIU4 Rev. #12 (08/23/11)  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Multiquip Appliance Trim Kit MVH 402GHB User Manual
Multiquip Automobile Parts QP 2TZ User Manual
Multiquip Music Mixer EM 90P User Manual
Multiquip Trash Compactor MVH R60H User Manual
Multiquip Welding System DLW 300ES User Manual